8 Parameter Process Data Object Formats

YASKAWA ELECTRIC

SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

29

„

IND

„

PWE

„

STW/ZSW

Bit

PPO Write

PPO Read

0

Sub-Index for parameter number
(F6-33 = 0)

Sub-Index for parameter number
(F6-33 = 0)

1
2
3
4
5
6
7
8

Sub-Index for parameter number
(F6-33 = 1)

Sub-Index for parameter number
(F6-33 = 1)

9

10
11
12
13
14
15

Bit

PPO Write

PPO Read

0 to 31

Setting Data

Error code when Response ID is 7
0: Incorrect PNU number
1: Write mode error
2: Lower or upper limit violated
3: Disabled IND is set
17: Write mode error during Uv condition or Write mode error during
parameter processing

Bit

PPO Write

PPO Read

0

OFF1: reserved

Ready to switch on: always 1

1

OFF2: reserved

Ready: always 1

2

OFF3: reserved

0: Not ready
1: Drive ready

3

Enable to RUN
0: Baseblock + Stop
1: Not Baseblock

0: No fault condition
1: Fault condition

4

0: STOP
1: RUN

Always 1

5

Ramp function generation enable: reserved

Always 1

6

Enable ramp function generator set-point: reserved

Switch-on inhibit: always 0

7

1: Fault Reset

0: No alarm condition
1: Alarm condition

8

0: Stop
1: JOG RUN forward (Fmax/10 speed)

0: No speed agree
1: Speed agree condition

9

0: Stop
1: JOG RUN reverse (Fmax/10 speed)

0: Local control
1: Control from PROFIBUS

10

0: Local control
1: Control from PROFIBUS

Always 0

11

Reserved

12
13
14
15