Option led display – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual

Page 9

Advertising
background image

4 Option Components

YASKAWA ELECTRIC

SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

9

‹

Option LED Display

The option has four bicolor, red/green LEDs to relay information about power, communication status, and errors. The
operational states of the LEDs after completion of the power-up diagnostic process are described in

Table 5

. Wait at least

2 seconds for the power-up diagnostic process to complete before verifying the states of the LEDs.

Table 4 Option LED States

Table 5 LED Operation After Power-up Diagnostic

{: On / †: Flashing /

×: Off

LED

Display

Operating Status

Remarks

Color

Status

RUN

(Power)

Green

ON

Power supply ON

Power is supplied to the option, and the option hardware self-diagnostics check
is complete.

OFF

Power supply OFF

• The drive has no power supply.
• Option and drive are not connected properly and/or no power is supplied to

the option.

• An internal, self-diagnostic error occurred in the option.

ERR

(Option Error)

Red

ON

Option error

Self-diagnostic error occurred in the option.

Flashing

Drive connection
error

Connection error between option and drive. This includes node address setting
errors to parameter F6-30 on the drive side.

OFF

Normal operation

Drive and option are properly connected.

COMM

(Communication

Status)

Green

ON

Communication
connected

Normal send/receive between the option and the PROFIBUS-DP master.

OFF

No data exchange

There is a problem establishing communication between the option and the
PROFIBUS-DP master.

BF

(PROFIBUS-DP

Error)

Red

ON

Waiting for
communication
procedure setting

Communication-related parameters are in the process of being set or initialized
by the PROFIBUS-DP master.

Flashing

Communication
setting error

Communication parameter error from PROFIBUS-DP master.

OFF

Normal operation

LED shuts off when the PROFIBUS-DP master is finished setting
communication-related parameters.

LED

Communication

Status

Possible Cause

Solution

RUN ERR COMM BF

×

×

×

× No power

Drive has no power.

Check all wiring to the drive, then turn on the power.

Option is not properly connected to the
drive or is not receiving enough power.

Shut off the drive and make sure the option is
connected properly. Turn the power back on.

{

×

×

×

• Checking

connection with
the drive

• Waiting for data

from the master

• Option is reading the node address or

parameter configuration.

• Waiting for initial input data from

master device.

×

{

×

×

Option self-
diagnostics error

The option is damaged.

Cycle power to the drive. If the LED status does not
change, replace the option.

×

†

×

×

Problem connecting
to the drive

• Problem initializing the drive and the

option.

• Incorrect node address.

• Cycle power to the drive. If the LED status does

not change, replace the option.

• Check the node address setting in the drive (F6-10)

{

×

×

{

Waiting for data
from the master
device

Waiting for data from the master device.
(Set_Parm_Message or
Chk_Cfg_Message)

• Check master network settings.
• Make sure the master device is operating normally.
• Check terminal resistance settings on the data line.
• Check for problems with the data line and

connector.

• Check if the data line is connected properly to

communication connector CN5.

{

×

×

†

Incorrect data or
option time out
waiting for data

The communication settings in the
master are set incorrectly.

Check the communication settings in the master.

{

×

{

×

Sending or
receiving data

Advertising