8 Parameter Process Data Object Formats

YASKAWA ELECTRIC

SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

31

MaxTsdr_9.6

60

60 Tbit = 6.25 msec

MaxTsdr_19.2

60

60 Tbit = 3.125 msec

MaxTsdr_45.45

60

60 Tbit = 1.32 msec

MaxTsdr_93.75

60

60 Tbit = 640 usec

MaxTsdr_187.5

60

60 Tbit = 320 usec

MaxTsdr_500

100

100 Tbit = 200 usec

MaxTsdr_1.5M

150

150 Tbit = 100 usec

MaxTsdr_3M

250

250 Tbit = 83 usec

MaxTsdr_6M

450

450 Tbit = 75 usec

MaxTsdr_12M

800

800 Tbit = 67 usec

Min_Slave_Interval

5

Minimum slave interval=0.5 ms

Freeze_Mode_supp 1

Freeze

mode not supported

Sync_Mode_supp 1

Sync

mode not supported

Fail_Safe

1

Fail safe supported

DPV1_Slave

1

DPV1_Data_Types 1
C1_Read_Write_supp

0

C2_Read_Write_supp

1

C2_Max_Data_Len

240

C2_Response_Timeout

100

C2_Read_Write_required

0

C2_Max_Count_Channels

1

Max_Initiate_PDU_Length

52

Modular_Station

1

Modular station.

Max_Module

1

Maximum # of modules: 1

Max_Input_Len

32

Maximum # of input bytes

Max_Output_Len

32

Maximum # of output bytes

Max_Data_Len

64

Maximum # of data bytes

Max_User_Prm_Data_Len 4
Ext_User_Prm_Data_Const(0) 0x40,0x01,0x00,0x01
Ext_User_Prm_Data_Ref(0)

1

Ext_User_Prm_Data_Ref(0)

2

Max_Diag_Data_Len

11

Maximum diagnostic length

Unit_Diag_Bit(0024)

“Undervoltage Condition”

Unit_Diag_Bit(0025)

“Inverter Communications Error”

Unit_Diag_Bit(0026)

“PNU915: Illegal PNU configured”

Unit_Diag_Bit(0027)

“PNU916: Illegal PNU configured”

Parameter

Setting Value

Note