5 EtherCAT® Option Components

YASKAWA Europe YEU TOEP C710606 98A - V1000 Option EtherCAT - Installation Manual

EN 13

Table E.5 UNDERSTANDING THE STATUS LEDS

LED

Color

Display

Meaning

Link Activity 1/2

-

Continuously Off

No link. The communication cable is not physically
connected. The EtherCAT

®

controller is not started up.

Green

Continuously On

The module is connected to Ethernet. A
communication cable is physically connected, but no
data are being exchanged.

Flickering

There is traffic on Ethernet, data are being exchanged

RUN

-

Continuously Off

The device is in Init state

Green

Blinking

The device is in Pre-Operational State (flashing rate
about 2.5 Hz)

Single flash

The device is in Safe-Operational State (one short flash
(approximately 200 ms) followed by a long off
condition (approximately 1000 ms)

Continuously On

The device is in Operational State

Red

Blinking

(1 Hz or 6 Hz)

The Option BOOT or APP firmware is executing the
NOID firmware loader.
1 Hz: Firmware loader protocol in IDLE state (waiting
for commands from the drive)
6 Hz: Firmware loader protocol is processing
commands.

ERR

Red

Continuously Off

No link. The EtherCAT

®

communication is in working

condition.

Blinking

General configuration error

Single flash

The slave device application has changed the
EtherCAT

®

state autonomously: The parameter

"Change" in the AL status register is set to 0x01:
change/error. Single flash is one short flash
(approximately 200 ms) followed by a long off phase
(approximately 1000 ms).

Double flash

The sync manager watchdog timeout has occurred.
Double flash is two short flashes (approximately 200
ms each), separated by an off condition (approximately
200 ms), and then a long off phase (approximately
1000 ms)

Continuously On

Possible causes:
1. An EtherCAT

®

PDI (Process Data Interface) error has

occurred, the NOID application interface has failed.
2. An option card FATAL event has occurred (system
has stalled execution, see EtherCAT

®

vendor object

0x4000 for the cause).

Blinking

(1 Hz or 6 Hz)

The option BOOT or APP firmware is executing the
NOID firmware loader.
1Hz: Firmware loader protocol in IDLE state (waiting
for commands from drive)
6Hz: Firmware loader protocol is processing
commands.