10 Fault Diagnosis and Possible Solutions

YASKAWA Europe YEU TOEP C710606 98A - V1000 Option EtherCAT - Installation Manual

EN 37

Minor Faults and Alarms

Table 6 lists up alarms that might occur during operation using a communication option
board. If a multi function digital output of the drive is programmed for H2- = 10, the
output will close if these alarms occur.

Digital Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solution

Communication wiring is faulty, there is a
short circuit, or something is not connected
properly.

Check for wiring errors.

 Correct the wiring.

 Remove and ground shorts and reconnect loose wires.

Programming error on the master side

 Check communications at start-up and correct programming errors.

Communication circuitry is damaged.

 Replace the drive if the fault continues to occur.

Digital Operator Display

Minor Fault Name

EEP

EEPROM Error
EEPROM checksum error

Cause

Possible Solution

Communication wiring is faulty, there is a

short circuit, or something is not connected

properly.

Check for wiring errors.

 Correct the wiring.

 Remove and ground shorts and reconnect loose wires.

EEPROM checksum error

If these errors occur, the object dictionary will be reset to its default
values.

 After the object dictionary has been changed and object dictionary
contents are then changed, execute a Store Parameter command (Index
= 1010 (Hex)).

 If the object dictionary has not been changed, execute a Restore
Parameter command (Index = 1011 (Hex)).