7 EtherCAT® Option Related Drive Parameters

7

EtherCAT

®

Option Related Drive Parameters

The drive parameters listed in

Table E.2

have influence on some functions of the SI-ES3

option card. Check these parameters before starting network communications.

Table E.2 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

Frequency
Reference
Selection

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse Input (Terminal RP)

<6>

b1-02

<1>

Run Command
Selection

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option card

1

E2-04

<2>

Motor 1 Motor
Poles

Set the number of motor poles described on the motor nameplate.
2 to 48

4

F6-01

Operation
Selection after
Communications
Error

Determines drive response when a bUS error is detected during
communications with the EtherCAT

®

Option

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<3>

1

F6-02

External Fault
Detection
Conditions (EF0)

Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation

0

F6-03

Stopping Method
for External Fault
from
Communication
Option Board

Determines drive response for external fault input (EF0) detection during
EtherCAT

®

communication

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<3>

1

F6-06

<4>

Torque Reference/
Torque Limit
selection from
Communications
Option

0: Torque reference/torque limit via network communications are
disabled.

1:

Torque reference/torque limit via network communications are

enabled.

<5>

0

F6-07

NetRef/ComRef
Selection Function

0: Multi-step speed reference disabled (F7 mode)
1: Multi-step speed reference allowed (V7 mode)

0