9 process data objects (pdo) – Yaskawa SI-ES3 for V1000 User Manual

Page 30

Advertising
background image

9 Process Data Objects (PDO)

EN 30

YASKAWA Europe YEU TOEP C710606 98A - V1000 Option EtherCAT - Installation Manual

Receive PDOs (RxPDO)

The Receive PDOs have a default mapping according to the table below. The end user can
re-map Receive PDOs by writing to the map objects 0x1600-1628, refer to
n Communication Profile Objects (DSP 301).

PDO number

Receive PDO Mapping

Mapped objects (Hex)

Index (Hex)

1

Sub-index 1: 0x6040#0, 2-bytes (DSP402 control word)

0x1600

2

Sub-index 1: 0x6040#0, 2-bytes (DSP402 control word)
Sub-index 2: 0x6060#0, 1-bytes, (DSP402 Modes of operation)

0x1601

6

Sub-index 1: 0x6040#0, 2-bytes (DSP402 control word)
Sub-index 2: 0x6042#0, 2-bytes, (vl target velocity)

0x1605

7

Sub-index 1: 0x6040#0, 2-bytes (DSP402 control word)
Sub-index 2: 0x60FE#1, 4-bytes, (Physical digital outputs)

0x1606

8

Sub-index 1: 0x6040#0, 2-bytes (DSP402 control word)
Sub-index 2: 0x6060#0, 1-bytes, (DSP402 Modes of operation)

0x1607

21

Sub-index 1: 0x6048#1, 4-bytes (vl Accel delta speed)
Sub-index 2: 0x6048#2, 2-bytes, (vl Accel delta time)

0x1614

22

Sub-index 1: 0x6049#1, 4-bytes (vl Decel delta speed)
Sub-index 2: 0x6049#2, 2-bytes, (vl Decel delta time)

0x1615

23

Sub-index 1: 0x604A#1, 4-bytes (vl quick-stop delta speed)
Sub-index 2: 0x604A#2, 2-bytes, (vl quick-stop delta time)

0x1616

24

Sub-index 1: 0x604C#1, 4-bytes (vl Dimension factor)
Sub-index 2: 0x604C#2, 4-bytes, (vl Dimension factor)

0x1617

36

Sub-index 1: 0x2000#1, 2-bytes (Operation command)

0x1623

37

Sub-index 1: 0x2010#1, 2-bytes (Speed reference/limit)

0x1624

38

Sub-index 1: 0x2020#1, 2-bytes (Torque reference/limit)

0x1625

39

Sub-index 1: 0x2030#1, 2-bytes (Torque compensation)

0x1626

40

Sub-index 1: 0x2040#1, 4-bytes (MEMOBUS/Modbus read request)

0x1627

41

Sub-index 1: 0x2050#1, 4-bytes (MEMOBUS/Modbus write request)

0x1628

Advertising