10 Fault Diagnosis and Possible Solutions

EN 34

YASKAWA Europe YEU TOEP C710606 98A - V1000 Option EtherCAT - Installation Manual

• Is the controller program working? Has the controller CPU stopped?
• Did a momentary power loss interrupt communications?

Faults

Table E.6

lists possible faults when using a communication option. The drive’s fault contact

will close if one of these faults occur.

Table E.6 Fault Display and Possible Solutions

Digital Operator Display

Fault Name

bUS

EtherCAT

®

Option Communication Error

After establishing initial communication, the connection was lost.
Only detected when the run command or frequency reference is
assigned to the option (b1-01=3 or b1-02=3).

Cause

Possible Solution

Master controller (PLC) has stopped
communicating.

Check for faulty wiring.

 Correct any wiring problems.

Communication cable is not connected
properly.

A data error occurred due to noise.

Check the various options available to minimize the effects of noise.

 Take steps to counteract noise in the control circuit wiring, main
circuit lines, and ground wiring.

 If a magnetic contactor is identified as a source of noise, install a
surge absorber to the contactor coil.

 Make sure the cable used fulfills the EtherCAT

®

requirements.

Ground the shield on the controller side and on the EtherCAT

®

Option

side.

EtherCAT

®

Option is damaged.

 If there are no problems with the wiring and the error continues to
occur, replace the EtherCAT

®

Option.

Digital Operator Display

Fault Name

EF0

External Fault Input from EtherCAT Option

The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent from the upper
controller (PLC).

 Remove the cause of the external fault.

 Reset the external fault input from the upper controller (PLC)
device.

Problem with the upper controller (PLC)
program.

 Check the program used by the upper controller (PLC) and make
the appropriate corrections.

Digital Operator Display

Fault Name

oFA00

EtherCAT Option Card Fault

The drive does not support the option board plugged in.

Cause

Possible Solution

Non-compatible option connected to the
drive.

 Check the drive option board compatibility. Replace the option card
if the fault persists even though the drive should support it.