0 changes from standard product 3.0 limitations – Yaskawa Motion Control G7 Drive Software User Manual

Page 4

Advertising
background image

Date: 05/16/08, Rev: 08-05

Page 4 of 38

TM.G7SW.117

Due to parameter limitations, the “User” access level and all of the associated “A2” parameters are
deleted.

3-Wire control is not allowed when the motion software is enabled.

Parameter b1-01 (Reference Source) is only effective when motion control is disabled (P1-01 = 0).
When motion control is enabled, parameter b1-01 is ignored, and the frequency reference originates
from the motion control routine.

Parameters d2-02 and d2-03 are disabled, which fixes the minimum output speed at 0%.

Accel and Decel ramp switching via multifunction digital input or via speed sensing is disabled when a
move is in progress. Accel and Decel ramp switch is controlled by the motion software during a move.

Encoder direction selection F1-05 is not available when encoder type is “Serial Abs Ch1” (P3-01 = 3).

PG Channel 2 parameters F1-21 and F1-22 have no effect when motion control is enabled.

All 230V units will have a default carrier frequency of 2.0 kHz. The maximum carrier frequency setting
on models G7U2075 and smaller is limited to 4.0 kHz.

The Motion Control algorithm is only available when the drive is in the Flux Vector control method
(A1-02 = 3).

The distance from home cannot exceed 10

9

encoder counts.

The 32 bit position monitor registers should be read using a “Read Multiple” Modbus command (03h)
to ensure that the data from high and low words are read together for an accurate reporting of position.

Using the 32 bit position command, the drive can now operate in a position beyond what the digital
operator can display.

The drive must be re-homed after a PG Open (PGo) fault occurs.

2.0

Changes from Standard Product

3.0

Limitations