Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual

Page 11

Advertising
background image

©

2015 Sensata Technologies

Page 4

Introduction

1.4 Battery Regulation Methods

In an AC-coupled system, there are several methods that are used to regulate the battery voltage,

as described below:
1. AC disconnect driven by DC controlled relays: When the battery voltage rises above a

maximum setpoint, a battery voltage controlled relay is activated to open the AC connection to

the grid-tie inverter. This causes the critical load sub-panel to now be powered from the batteries

through the battery-based inverter. When the battery voltage falls to the low setpoint, the relay

closes and allows the grid-tie inverter to reconnect and begin generating power from the renewable

energy. If the battery voltage rises again, this cycle repeats.
Disadvantages:

• Batteries are cycled, not regulated—does not allow the batteries to be properly charged.
• Generated power from the renewable energy is wasted while the relay is opened.
• The DC relay setpoints must be set much higher than required to ensure the DC relay

doesn’t connect or interfere with normal charging (from the battery-based inverter) and

any sell back voltage settings once the utility power returns.

• No temperature-compensated regulation while charging.

2. DC diversion driven by DC controlled relays: When the battery voltage rises above a

maximum setpoint, a battery voltage controlled relay is used to switch on a dedicated DC diversion

load to consume any excess power. When the battery voltage falls to the low setpoint, the dedicated

diversion load turns off. If the battery voltage rises again, this cycle repeats.
Disadvantages:

• Batteries are cycled, not regulated—does not allow the batteries to be properly charged.
• Diffi cult to source and size DC diversion loads to absorb the full output of the renewable

energy source.

• The regulation setpoint must be set much higher than required to ensure the diversion load

is not always in “regulation”, and that it doesn’t interfere with normal charging (from the

battery-based inverter) or any sell back voltage settings once the utility power returns.

• Since excess power is regulated on the DC side, the battery-based inverter is required to be

always on, re-converting the renewable energy from AC back to DC where it is diverted—an

extra conversion step creates energy loss and there is an unnecessary use of the inverter.

• No temperature-compensated regulation while charging.

3. DC Diversion Controller off the battery: When the battery voltage rises above a voltage

regulation setpoint, the DC Diversion Controller sends excess current to a dedicated DC diversion

load to maintain the battery voltage. When the battery voltage falls below the regulation setpoint,

current is no longer sent to the dedicated diversion load.
Disadvantages:

• Diffi cult to source and size DC diversion loads correctly. If the load is too small, it cannot divert

enough power from the source (wind, hydro, etc.), and the battery could be overcharged. If
the diversion load is too large, it will draw more current than the rating of the controller—
causing damage or causing the controller’s protection circuits to open the load.

• Multiple controllers are usually needed even for medium sized renewable energy systems

(i.e., a 4kW/48VDC system requires at least a 70-amp controller).

• The regulation setpoint must be set much higher than required to ensure the diversion load

is not always in “regulation”, and that it doesn’t interfere with normal charging (from the

battery-based inverter) or any sell back voltage settings once the utility power returns.

• Since excess power is regulated on the DC side, the battery-based inverter is required to be

always on, re-converting the renewable energy from AC back to DC where it is diverted—this

extra conversion step creates energy loss and there is an unnecessary use of the inverter.

Advertising