Safety Information

Page ii

IMPORTANT PRODUCT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR THE ACLD-40 CONTROLLER THAT SHALL

BE FOLLOWED DURING THE INSTALLATION AND OPERATION OF THIS PRODUCT. Before using

the ACLD, read all instructions and cautionary markings. Also, be sure to follow the instructions

provided for each component of the system. Do not perform any installation or service described

in this owner’s manual unless properly trained and capable. Incorrect installation or service may

result in the risk of electric shock, fire, or other safety hazard.

Safety Symbols

The following safety symbols have been placed throughout this manual to indicate dangerous and

important safety instructions.

WARNING: This symbol indicates that failure to take a specifi ed action could result in

physical harm to the user.

CAUTION: This symbol indicates that failure to take a specifi ed action could result in

damage to the equipment.

Info: This symbol indicates information that emphasizes or supplements important

points of the main text.

Safety Precautions

• All electrical work must be performed in accordance with local and national electrical codes.
• This product is designed for indoor/compartment installation. It must not be exposed to rain,

snow, moisture, or liquids of any type.

• Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
• There are no user-serviceable parts contained in this product.
• This unit is provided with integral protection against overloads.
• Use Class 1 wiring methods for field wiring connections to terminals of a Class 2 circuit.
• Listed or labeled equipment shall be installed and used in accordance with any instructions

included in the listing or labeling.

• Always verify proper wiring prior to turning on the ACLD.
• Use only copper wires with a minimum temperature rating of 75°C (167°F).
• AC wiring must be no less than #10 AWG (5.3 mm

2

) gauge copper wire.

• Torque all AC wiring connections to the required values.
• The ACLD must be properly mounted, see Section 2.3 “Mounting the ACLD” in this manual.

• Protection for the AC output wiring against overcurrent is not included in the ACLD and must

be provided as part of the system installation. Refer to Section 2.8 “Wiring the ACLD” for more

information.

• The AC output neutral conductor is not connected (bonded) to the ACLD chassis. Both the input

and output conductors are isolated from the ACLD chassis. System grounding, if required, is

the responsibility of the system installer and must comply with local and national electrical

codes and standards.