0 troubleshooting – Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual

Page 40

Advertising
background image

Page 33

©

2015 Sensata Technologies

Troubleshooting

4.0 Troubleshooting

This section will help you troubleshoot the ACLD when it has a fault condition. The ACLD will indicate

a particular abnormal/fault condition by how many times the Status LED blinks before pausing. To

determine the fault condition, monitor the Status LED indicator for at least 10 seconds and count

the number of blinks that occur before the LED turns off for four seconds. After determining the

number of blinks, refer to the information below to help diagnose/clear the condition.

Blinks On 1 time

then off four seconds

-

High Current Fault; the current is at least 30%

above rated current.

Remedy: Ensure that the load is connected and sized correctly. If the load is correct,

reset the unit. The unit is reset by pressing the ON/OFF switch on the side of the ACLD

controller to the OFF position (this removes power to the unit). After power is removed,

press the ON/OFF switch to the ON position again to restore power. If the fault recurs,

contact Sensata for service.

Blinks On 2 times

then off four seconds

-

High VAC In Fault; a very high AC voltage

(>275 VAC) has been detected on the AC input.

Remedy: This fault automatically clears once the AC input voltage to the ACLD falls

below 260 VAC.

Blinks On 4 times then off four seconds - No Load Fault; no loads detected on either

output terminals (detected by minimum current fl ow to loads).

Remedy: Check to ensure that the loads are rated for 240 VAC, sized correctly (see Section

2.9.2 on load sizing criteria), and connected to the correct output terminals (see Figure 2-5).

The loads should have a resistance between 10-15 ohms (see to Figure 3-11).

Primary

Load

Secondary

Load

Ohmmeter

Use an ohmmeter to check resistance

from terminal 7 to 8 (primary load),

then from terminal 9 to 10 (secondary

load). The resistance for each load

connected should be ~10-15 ohms.

CAUTION: Ensure all power to the

ACLD is removed prior to checking

the load resistance or damage to

the ohmmeter may occur.

ACLD-40

Figure 3-11, Checking Load Resistance

Advertising