Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual

Page 20

Advertising
background image

Page 13

©

2015 Sensata Technologies

Installation

2.4 General Wiring Requirements

This section describes the requirements and recommendations for wiring the ACLD controller.

Before wiring the controller, carefully read all instructions.
Wiring should meet all local codes and standards and be performed by qualifi ed personnel

such as a licensed electrician.
The NEC (National Electric Code, ANSI/NFPA 70) for the United States and the CEC (Canadian

Electrical Code) for Canada provide the standards for safely wiring residential and commercial

installations. The NEC (or CEC) lists the requirement for wire sizes, overcurrent protection, and

installation methods and requirements.

WARNING: Because the ACLD is wired with an inverter/charger, there is power from

multiple sources (inverter, generator, utility, batteries, solar arrays, etc.) which make

the wiring more hazardous and challenging. Ensure they are all de-energized (i.e.,

breakers opened, fuses removed) before proceeding—to prevent accidental shock.

2.4.1

Protecting Wire – Conduit Box

The AC wires to and from the load controller must be protected as required by code. This can be

done by using jacketed wires or by feeding the wires through conduit. A conduit box (MPX-CB) is

available that allows the AC conduit to be connected to the ACLD controller.

2.4.2 Wiring

Requirements

• All conductors that are at risk for physical damage must be protected by conduit, tape, or

placed in a raceway.

• Always check for existing electrical, plumbing, or other areas of potential damage prior to

making cuts in structural surfaces or walls.

AC overcurrent protection must be provided as part of the installation and be properly sized.

• Use only copper wires with a minimum temperature rating of 75°C (167°F).
• Always use properly rated circuit breakers. If using an electrical sub-panel, circuit breakers

can be moved from the main electrical panel to the sub-panel only if the breakers are also

listed to be installed in the sub-panel.

• Wiring must be no less than #10 AWG (5.3 mm

2

) gauge copper wire and be approved for

the application (i.e., residential wiring).

• The wire sizes recommended in this manual are based on the ampacities given in Table

310.16 (in conduit) or Table 310.17 (in free air) of the NEC, ANSI/NFPA 70, for 75°C (167°F)

copper wire based on an ambient temperature of 30°C (86°F).

2.4.3 Wire

Routing

Before connecting any wires, determine all wire routes to and from the load controller. Typical

routing scenarios are:

• Network communication cable from the inverter to the load controller.
• AC wiring from the inverter output to the load controller.
• AC wiring from the load controller to circuit protection (if not using the MMP enclosure)

AC wiring from the circuit protection (or MMP enclosure) to the AC sub-panel (i.e., dedicated

inverter circuits).

• AC output wiring from the load controller to the primary diversion load (which can be

confi gured to turn off).

• AC output wiring from the load controller to the secondary diversion load (which must be

confi gured to always be available and stay on).

• Ground wiring to and from the load controller.
• Remote control cable to the inverter.

Advertising