Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual

Page 18

Advertising
background image

Page 11

©

2015 Sensata Technologies

Installation

WALL MOUNTED

(Fan facing down and MPX-CB installed)

When the unit is mounted in this position,

either the MPX-CB (MPX conduit box) or

MMP Series Enclosure must be attached

below.

2.3 Mounting the ACLD Controller

When mounting the ACLD controller, the surface and the mounting hardware must be capable of

supporting at least twice the weight of the unit. To meet regulatory requirements, the ACLD must

be mounted in one of the following positions (as shown in Figure 2-3):
• above or under a horizontal surface (shelf or table),
• on a vertical surface (wall) with the intake cooling fan to the right,
• on a vertical surface (wall) with the intake cooling fan toward the bottom, and an optional

MPX-CB (conduit box) installed below the controller.

Info: The four mounting holes on the ACLD have a diameter of 0.280” (7.11 mm), good

for 1/4” bolts/screws (see Figure 2-4 for hole locations).

Info: The MPX-CB prevents material from falling out the bottom in the event of an

internal fi re, and also allows suffi cient ventilation to prevent the ACLD controller from

overheating under normal operating conditions.

Info: Sensata provides a backplate that can be used to mount the ACLD (and if required,

the MPX-CB). This backplate part number is BP-S (Back Plate - Single).

After determining the mounting position, refer to the physical dimensions as shown in Figure 2-4

or use the base of the ACLD as a template to mark your mounting screw locations. After marking

the mounting screw locations, mount the controller with appropriate mounting hardware.

Figure 2-3, Approved Mounting Positions

SHELF OR TABLE MOUNTED

(Fan facing away from wall)

WALL MOUNTED

(Fan to the right)

Advertising