Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual

Page 17

Advertising
background image

©

2015 Sensata Technologies

Page 10

Installation

2.2 Locating the ACLD Controller

Only install the ACLD controller in a location that meets the following requirements:
Clean and Dry – The controller should not be installed in an area that allows dust, fumes, insects,

or rodents to enter or block the controller’s ventilation openings. This area also must be free from

any risk of condensation, water, or any other liquid that can enter or fall on the controller. Failure

due to any of the above conditions is not covered under warranty.

Info: If the controller is installed in an area where moisture may occur, we recommend

putting silicone dielectric grease compound into the electrical ports (as shown in Figure

1-3, Items 2 and 3). Before installing the cables, or if leaving any ports open, squirt a

liberal amount into each port. Silicone dielectric compound makes an

effective moisture

and corrosive barrier to help protect and prevent corrosion to the RJ11 connections.

Cool – The controller should be protected from direct sun exposure or equipment that produces

extreme heat. If the ambient temperature around the controller exceeds 77°F (25°C), the power

specifi cations are reduced.
Ventilation – In order for the controller to provide full output power and to avoid over-temperature

fault conditions, do not cover or block the controller’s ventilation openings or install this controller

in an area with limited airfl ow. The controller uses a fan to provide forced air cooling, this fan pulls

in air through the intake opening (see Figure 1-3, Item 5) and blows out air through the exhaust

vents (see Figure 1-4, Item 7). Allow at the minimum an airspace clearance of 6” (15.2 cm) at

the intake and exhaust vents, and 3” (7.6 cm) everywhere else to provide adequate ventilation.
Safe – Keep any fl ammable/combustible material (i.e., paper, cloth, plastic, etc.) that may be

ignited by heat, sparks, or fl ames at a minimum distance of 2 feet (61 cm) from the controller.
Have access to the MS-PAE Series inverter – The communications control for the ACLD is provided

by the MS-PAE Series inverter, so the ACLD controller must be in an area that allows the network

cable to be connected to the inverter. The network cable provided is 6’ and can be extended up to a

length of 200 feet without data degradation. See Section 2.10.1 for more information on the cable.
Accessible Do not block access to the controller’s inverter and network ports, as well as the

ON/OFF switch and status indicator. Allow enough room to access the AC wiring terminals and

connections, as they will need to be checked and tightened periodically.
Away from sensitive electronic equipment – High powered devices with PWM circuitry can

generate levels of RFI (Radio Frequency Interference). Locate any electronic equipment susceptible

to radio frequency and electromagnetic interference as far from the controller as possible.

2.2.1 Conduit

Knockouts

The ACLD controller

comes standard with four dual knockouts (for 1/2” and 3/4” conduits) on each

side (eight total). Figure

1-3 shows the location of these conduit knockouts.

Select the appropriate

knockout that is close to the terminal that the wire will connect to, or whichever one works for the

way your fi eld wiring comes in.

Info: The knockouts can be easily removed by tapping the edge with a straight bladed

screwdriver and a hammer, then

twist out with pliers. See Figure 2-2.

Before removing any knockouts and mounting the ACLD controller, think about whether you are

going to use

cable clamps or conduit (using the optional MPX-CB conduit box), and

the different

wiring required. See Section 2.4.3 for wire routing requirements to/from the ACLD controller.

Figure 2-2, Removing

Knockouts

Advertising