Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual

Page 41

Advertising
background image

©

2015 Sensata Technologies

Page 34

Troubleshooting

Troubleshooting Continued:

Blinks On 5 times then off four seconds - Desat (i.e. Desaturation) Fault; hardware

saturation inside the controller has occurred—indicates a possible catastrophic failure.

Remedy: This fault requires a reset of the ACLD. Press the ON/OFF switch on the side

of the ACLD controller to remove power to the unit, and then press the ON/OFF switch

again to restore power. If the fault recurs, contact Sensata for service.

Blinks On 7 times then off four seconds - Overcurrent Fault; the current has reached

an extremely high level (about twice the rated current).

Remedy: This fault could be the result of too big of a load. Ensure the loads are sized

and connected correctly. Press the ON/OFF switch on the side of the ACLD controller to

remove power to the unit, and then press the ON/OFF switch again to restore power.

(See Section 2.9.2 on load sizing criteria).

Blinks On 8 times then off four seconds - Output Short Fault; a shorted output to loads

has been detected.

Remedy: Check to ensure that the loads are sized and connected correctly. See Section

2.9.2 on load sizing criteria. Refer to Figure 3-11 to check the load resistance.

Blinks On 9 times

then off four seconds

-

Overtemp Fault; the internal temperature of

the ACLD

controller has risen above

90°C.

Remedy: This fault can be

caused by loads too great for the controller to operate

continuously (s

ee Section 2.9.2 on load sizing criteria)

or by the lack of ventilation to

the controller (check for objects in front of the fan grill). O

nce the temperature falls

below 70°C, the fault automatically clears and the ACLD will resume operation.

Blinks On 10 times then off four seconds - No Comm condition; the ACLD does not

detect nor is able to communicate with the inverter/network.

Remedy: Disconnect the remote communications cable from the inverter for 5 seconds,

and then reconnect it (see Figure 2-8). If the fault continues, then check/replace the

remote cable. Ensure this cable is 4-wire telephone cable (see Figure 2-9). This fault will

automatically clear once the ACLD starts communicating with the inverter.

Advertising