005C Battery is weak

Event Type

Warning

Cause

The Battery Backup Unit periodically evaluates the health of the battery and
its ability to backup the 3ware RAID controller in case of a power failure.
This message is posted when the result of the health test is below the warning
threshold.

Action

Replace the battery pack if warnings persist.

005D Battery health check failed

Event Type

Error

Cause

The Battery Backup Unit is not able to backup the 3ware RAID controller.

The Battery Backup Unit periodically evaluates the health of the battery and
its ability to backup the 3ware RAID controller in case of a power failure.
This message is posted when the result of the health test is below the fault
threshold.

Action

Replace the battery pack. The BBU cannot presently backup the controller.

005E Cache synchronization completed

Event Type

Information

Cause

The 3ware RAID controller performs cache synchronization when system
power is restored following a power failure. This message is posted for each
unit when the cache synchronization completes successfully.