Module Configuration
MVI56-BSAPS ♦ ControlLogix Platform
Bristol Babcock Serial Slave Module
ProSoft Technology, Inc.
Page 35 of 83
September 22, 2008
The DPC 3330 supports command types "SEND", "POLL" AND
"POLL+SEND"
The ProSoft BSAPS driver ONLY supports "SEND" and "POLL"
A "POLL+SEND" will not work.
The DPC 3330 "Inlist" must match the ProSoft "BSAPS Data Element" list
For the DPC 3330 to read and write to the ProSoft BSAPS – enabled device,
both a Master Module "Mode 0" (Poll) AND "Mode 1" (Send) must be defined
within ACCOL Workbench
The following illustration shows an example of the ACCOL Workbench defining
both a Master Module "Mode 0" (Poll) AND "Mode 1" (Send).
Advertising