ProSoft Technology MVI56-BSAPS User Manual

Page 71

Advertising
background image

Reference MVI56-BSAPS

♦ ControlLogix Platform

Bristol Babcock Serial Slave Module

ProSoft Technology, Inc.

Page 71 of 83

September 22, 2008

Offset Content

Description

220

Number of responses:
Port 2

Contains the total number of messages received on the
port.

221

Number of errors sent:
Port 2

Contains the total number of message errors sent out
the port.

222

Number of errors received:
Port 2

Contains the total number of message errors received
on the port.

223

Backplane Transfer Writes Contains the total number of write blocks transferred

from the processor to the module.

224

Backplane Transfer Reads Contains the total number of read blocks transferred

from the module to the processor.

225

Backplane Blocks Parsed

226

Backplane Transfer Errors Contains the total number of block errors recognized by

the module.

227

Current Error: Port 1

For a slave port, this field contains the value of the
current error code returned. For a master port, this field
contains the index of the currently executing command.

228

Last Error: Port 1

For a slave port, this field contains the value of the last
error code returned. For a master port, this field contains
the index of the command with the error.

229

Current Error: Port 2

For a slave port, this field contains the value of the
current error code returned. For a master port, this field
contains the index of the current executing command.

230

Last Error: Port 2

For a slave port, this field contains the value of the last
error code returned. For a master port, this field contains
the index of the command with an error.

A data file should be allocated in the ladder logic to hold this block of data. The
size of the block of data is 35 words.

Advertising