Normal Data Transfer

Normal data transfer includes the paging of the user data found in the module's
internal database in registers 0 to 2740 and the status data. These data are
transferred through read blocks (input image). Write blocks (output image)
transfer data into module's internal database in register 3000 to 5740. These
data are gathered in a response command to a master. The Module Setup
section provides a description of the data objects used with the blocks and the
ladder logic required. The structure and function of each block is described in the
following topics.

Read Block
These blocks of data transfer information from the module to the ControlLogix
processor. The structure of the input image used to transfer this data is shown in
the following table.

Offset Description

Length

0 Reserved

1

1

Write Block ID

1

2 to 201

Read Data

200

202

Program Scan Counter

1

203 to 204

Product Code

2

205 to 206

Product Version

2

207 to 208

Operating System

2

209 to 210

Run Number

2

211 to 214

Port 1 Error Status

4

215 to 218

Port 2 Error Status

4

219 to 224

Data Transfer Status

6

225

Port 1 Current Error/Index

1

226

Port 1 Last Error/Index

1

227

Port 2 Current Error/Index

1

228

Port 2 Last Error/Index

1

229 to 248

Spare

20

249

Read Block ID

1

The Read Block ID is an index value used to determine the location of where the
data will be placed in the ControlLogix processor controller tag array of module
read data. Each transfer can move up to 200 words (block offsets 2 to 201) of
data. In addition to moving user data, the block also contains status data for the
module. This last set of data is transferred with each new block of data and is
used for high-speed data movement.

The Write Block ID associated with the block requests data from the ControlLogix
processor. Under normal program operation, the module sequentially sends read
blocks and requests write blocks. For example, if three read and two write blocks
are used with the application, the sequence is as follows:

R1W1

→ R2W2 → R3W1 → R1W2 → R2W1 → R3W2 → R1W1