5.9 Absolute Encoders

5-63

5

Op

er

at

io

n

5.9.4

Absolute Encoder Setup

Setting up the absolute encoder is necessary in the following cases.

• When starting the machine for the first time
• When an encoder backup error alarm (A.810) is generated
• When an encoder checksum error alarm (A.820) is generated
• When initializing the rotational serial data of the absolute encoder

Set up the absolute encoder with Fn008.

(1) Precautions on Setup

• If the following absolute encoder alarms are displayed, cancel the alarm by using the same method as the

absolute encoder setup. They cannot be canceled with the SERVOPACK alarm reset input signal (/ALM-

RST).

• Encoder backup error alarm (A.810)
• Encoder checksum error alarm (A.820)

• Any other alarms (A.8

) that monitor the inside of the encoder should be canceled by turning OFF the

power.

(2) Preparation

The following conditions must be met to setup the absolute encoder.

• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be OFF.

(3) Operating Procedure

Use the following procedure.

CAUTION

• The rotational data will be a value between -2 and +2 rotations when the absolute encoder setup is exe-

cuted. The reference position of the machine system will change. Set the reference position of the host

controller to the position after setup.

If the machine is started without adjusting the position of the host controller, unexpected operation may

cause injury or damage to the machine. Take sufficient care when operating the machine.

Step

Panel Display

Keys

Description

1

Press the

Key to select the utility function mode

(Fn

). And press the

or

Key to select

the Fn008.

2

Press the

Key to view the execution display of

Fn008.

3

Keep pressing the

Key until "PGCL1" is

changed to "PGCL5."

4

Press the

Key to setup the absolute encoder.

After completing the setup, "DONE" is flashed for
approximately one second and "BB" is displayed.

5

Press the

Key to return to the display of the pro-

cedure 1.

6

To enable the change in the setting, restart the SERVOPACK.

B B
F n 0 0 6 : A l m H i s t C l r
F n 0 0 8 : M t u r n C l r
F n 0 0 9 : R e f A d j
F n 0 0 A : V e l A d j

-

F U N C T I O N

-

B B

M u l t i t u r n C l e a r

P G C L 1

B B

M u l t i t u r n C l e a r

P G C L 5

B B

M u l t i t u r n C l e a r

P G C L 5

B B
F n 0 0 6 : A l m H i s t C l r
F n 0 0 8 : M t u r n C l r
F n 0 0 9 : R e f A d j
F n 0 0 A : V e l A d j

-