Yaskawa Σ-V Series AC Servo Drives Rotational Motor Analog Voltage Reference User Manual

Page 302

Advertising
background image

10 Appendix

10.2.2 Parameters

10-20

Pn50A

2

Input Signal Selection 1

0000 to FFF1

2100

After restart

Setup

(cont’d)

Parameter

No.

Size

Name

Setting

Range

Units

Factory

Setting

When

Enabled

Classification

Reference

Section

4th 3rd 2nd 1st

digit digit digit digit

n.

Input Signal Allocation Mode

Reference

Section

0

Uses the sequence input signal terminals with the factory-set allocations.

3.3.1

1

Changes the sequence input signal allocation for each signal.

Servo ON (/S-ON) Signal Mapping
Signal Polarity: Normal; Servomotor power ON when ON (L-level)
Signal Polarity: Reverse; Servomotor power OFF when OFF (H-level)

Reference

Section

0

Active when CN1-15 input signal is ON (L-level).

5.2.1

1

Active when CN1-16 input signal is ON (L-level).

2

Active when CN1-17 input signal is ON (L-level).

3

Active when CN1-18 input signal is ON (L-level).

4

Active when CN1-25 input signal is ON (L-level).

5

Active when CN1-26 input signal is ON (L-level).

6

Active when CN1-12 input signal is ON (L-level).

7

Always active (fixed).

8

Not active (fixed).

9

Active when CN1-15 input signal is OFF (H-level).

A

Active when CN1-16 input signal is OFF (H-level).

B

Active when CN1-17 input signal is OFF (H-level).

C

Active when CN1-18 input signal is OFF (H-level).

D

Active when CN1-25 input signal is OFF (H-level).

E

Active when CN1-26 input signal is OFF (H-level).

F

Active when CN1-12 input signal is OFF (H-level).

/P-CON Signal Mapping (P control when ON (L-level))

Reference

Section

0 to F

Same as Servo ON Signal (/S-ON) Mapping.

6.9.3

P-OT Signal Mapping (Forward run prohibited when OFF (H-level))

Reference

Section

0

Forward run allowed when CN1-15 input signal is ON (L-level).

5.2.3

1

Forward run allowed when CN1-16 input signal is ON (L-level).

2

Forward run allowed when CN1-17 input signal is ON (L-level).

3

Forward run allowed when CN1-18 input signal is ON (L-level).

4

Forward run allowed when CN1-25 input signal is ON (L-level).

5

Forward run allowed when CN1-26 input signal is ON (L-level).

6

Forward run allowed when CN1-12 input signal is ON (L-level).

7

Forward run prohibited.

8

Forward run allowed.

9

Forward run allowed when CN1-15 input signal is OFF (H-level).

A

Forward run allowed when CN1-16 input signal is OFF (H-level).

B

Forward run allowed when CN1-17 input signal is OFF (H-level).

C

Forward run allowed when CN1-18 input signal is OFF (H-level).

D

Forward run allowed when CN1-25 input signal is OFF (H-level).

E

Forward run allowed when CN1-26 input signal is OFF (H-level).

F

Forward run allowed when CN1-12 input signal is OFF (H-level).