MGE UPS Systems GALAXY PW 225KVA User Manual

Page 16

Advertising
background image

1.4

Different Types of Galaxy PW™ Systems

1.4.1

Single UPS System

Figure 1-2: Galaxy PW™ Single UPS System.

Note: *The Fuse is to protect against catastrophic rectifier/inverter semiconductor failure.

1.4.2

Parallel UPS System

Parallel UPSs can be utilized when increased power is required (two to four parallel units), or an external bypass
must be added.

CAUTION

PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-
nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is
open, each UPS control panel display will show a message “LOAD
PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the
critical load is not protected because it is supplied by the maintenance
bypass power.

Legend:

Q1

(Molded CB NA): Isolation of
the rectifier/charger (A) from
the normal AC source (1);
rectifier/charger (A) start-up.

QF1

(circuit breaker): Battery (D)
protection and isolation.

Q5N

(switch): Isolation of the UPS
(B) from the load.

Q4S

(switch): Isolation of the static
bypass (C) from the bypass
AC source (2).

Q3BP

(switch): Bypass switch for
maintenance.

FUE

(fuses): Protection of the
rectifier/charger (A) from the
normal AC source.

FUS

(fuses): Protection of the
inverter (B) from the load.
Switch Q3BP is lock on open
position on parallel UPS
systems constituted to
increase available power.

maintenance bypass:
Q3BP

inverter (B):
DC to AC
power

isolation:
Q4S

isolation and
protection:

Q5N

rectifier/
charger (A):
AC to DC
power

QF1: isolation
and protection

normal
AC input

load

battery (D):
backup power

static bypass (C):

bypass
AC input

Q1

isolation
and
protection

(1)

(2)

harmonic
fliter

*FUSE

*FUSE

Galaxy PWUPS 100 to 225kVA

Introduction

1 — 4

86-133060-00 A00