1.6.2

Bypass AC Source

The parameters given in Table 1-2 and 1-2A can be used to determine the required rating of the upstream protec-
tive circuit breaker on bypass AC input.

NOTE

If the installation includes a transformer on the bypass AC input, allow for the
inrush current caused by magnetization of the transformer windings.

Table 1-2: Electrical Parameters for Bypass AC Source.

Electrical parameters for bypass AC source (480 V)

rated UPS

current bypass AC source (1)

output

rated current In for unit:

for 25%

for 50%

in kVA

overload

overload (3)

100

120

150

180

130

156

205

234

150

180

236

270

180

217

283

325

200

241

316

362

225

271

320

407

(1) The bypass AC source currents have been determined for a rated phase-to-phase voltage of 480 V, a load

power factor of 0.9 and for full rated load as well as overloads of 25% or 50%. When choosing the circuit breaker
rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the
data in the overload columns. See table and chart below.

Table 1-2A:

UPS output

maximum permissible current

in kVA

100

50 In for 20 ms

130

38 In for 20 ms

150

33 In for 20 ms

180

27 In for 20 ms

200

25 In for 20 ms

225

22 In for 20 ms

Figure 1-3: Fuse Curve Chart.

10

4

t(s)

I(A)

10

3

10

2

10

1

1

10-

1

10-

4

10-

3

10-

2

10

2

10

3

10

4