4.2.2

Operation with the Normal AC Source Down

In the event of a normal AC source failure or voltage outside specified tolerances of ±10% in amplitude (±15%
optionally), the rectifier/charger (A) stops and the battery (D) supplies the necessary backup power to the load via
the inverter (B).

The battery, float-connected between the rectifier/charger and the inverter, discharges during this operating mode:

lights 2 , 4 and 5 shine green.

The user is warned of battery operation by the slow beeping of the buzzer 6 , see Figure 4-6, and the message
"LOAD PROTECTED, BATTERY DISCHARGING", followed by the remaining backup time and the percent load.

This information is also available via volt-free changeover contacts for remote control devices.

Figure 4-6: Normal AC Source Indicator Diagram.

2

1

4

5

2

1

2

AB

C

D

Galaxy PWUPS 100 to 225kVA

Operation

4 — 4

86-133060-00 A00