Installation and user manual – MGE UPS Systems GALAXY PW 225KVA User Manual

Page 39

Advertising
background image

Installation and User Manual

3.5.3

Connections Between MUSI Boards

These connections are made using the special cables (A) supplied, see Figures 3-5.

1.

Connectors XM5, XM6 and XM7 on the MUSI board are used to transmit signals.

2.

Connectors XM10, XM11 and XM12 on the MUSI board are used to receive signals.

3.

Connector XM5 is associated with connector XM10 for communication with one UPS unit; similarly, XM6 is
associated with connector XM11 for communication with a second UPS unit and XM7 is associated with
connector XM12 for communication with a third UPS unit.

For connection with two parallel UPS units, see Figure 3-5.

For connection with three parallel UPS units, see Figure 3-6, page 3—6.

For connection with four parallel UPS units, see Figure 3-7, page 3—6.

IMPORTANT

Outside the cabinets, group the "UPOZ" inter-board and "MUSI" inter-board
connections with the inter-cabinet auxiliary connections, and separate this
assembly using power cables.

Figure 3-5: Two Parallel UPS Units Connections.

'MUSI'

Galaxy PW

TM

1

'MUSI'

Galaxy PW

TM

2

A

XM10

XM11

XM12

XM5

XM6

XM7

XM10

XM11

XM12

XM5

XM6

XM7

Installation

3 — 5

86-133060-00 A00