Installation and User Manual

3.8.1

"Temperature Monitor" installation in a Battery Room

The "Temperature Monitor" should be secured against a wall or any vertical support. See Figure 3-10.

1.

Choose a location near the batteries and away from draughts which adversely affect the accuracy of
temperature measurements. Dimensions: 75 x 75 x 21 mm.

2.

Use the holes provided in the base plate to screw the unit to the vertical support, unless the connecting cable
runs on the surface, break the knock-out in the unit base plate provided for cable entry. Secure the cable by
suitable means so that it does not pull on the unit.

Figure 3-10: Temperature Monitor" Base.

Mounting Hole

Cable Entry

Mounting Hole

Dimensions: 75 x 75 x 21 mm

board

Installation

3 — 11

86-133060-00 A00