Installation and User Manual

Start-up

Following servicing, proceed in the following order: (See Figure 5-3)

1.

Close switch Q1, then after approximately ten seconds, switches QF1, Q5N and Q4S,

2.

0pen bypass switch Q3BP,

3.

Start the inverter (press the "inverter ON" button 7 ).

Figure 5-1: UPS Isolation Diagram for Normal AC Bypass Source.

Figure 5-2: Panel Procedures for UPS Isolation.

Figure 5-3: Start-up After Isolation Procedure is Completed.