MGE UPS Systems GALAXY PW 225KVA User Manual

Page 87

Advertising
background image

Installation and User Manual

THE NUMBER OF UPS READY IS INSUFFICIENT,

LOAD TRANSFER IN STANDBY

This message may be displayed in non-redundant, parallel UPS systems, when the number of ready inverters in
not sufficient to supply the load.

INVERTER NOT CONNECTED

This message may be displayed in parallel UPS systems, when the inverter is not connected to the load.

PARALLEL UPS,

FORCED TRANSFER INHIBITED

This message is displayed when forced connection is requested on a parallel UPS system for a power extension.

INTERNAL UPS FAULT,

SELF-TEST FAULT

Communication between the system and the display is faulty. The buzzer sounds slowly and discontinuously.

FORCED TRANSFER TO M2 REQUESTED,

POWER TO LOAD MAY BE INTERRUPTED

CONFIRM YOUR REQUEST WITH KEY

ø

This message is displayed following pressing of the "forced-transfer" key 20, when the load is supplied via the inverter.

UPS SUPPLIED BY A GENERATOR SET

This message informs the user that the UPS has received the order to limit the current drawn by the rectifier/charger.
It is displayed when the corresponding signal is transmitted by the remote indications board which must be
conFigure d for this function.

VENTILATION FAULT

This message is displayed when a fault occurs on a fan.

Appendices

A — 9

86-133060-00 A00