MGE UPS Systems GALAXY PW 225KVA User Manual

Page 42

Advertising
background image

"load on battery power" signal:

(Volt-free changeover contact) indicating that the inverter is supplied
by the battery in the following cases:

- normal AC source outage or voltage drop.

- rectifier/charger shutdown.

- rectifier/charger current limiting.

This signal, which may be used to initiate process saving and shutdown
procedures, is time-delayed 30 seconds to avoid unnecessary operations
following micro-breaks.

"Maintenance position" signal:

(Volt-free changeover contact) indicating that:

- maintenance bypass switch Q3BP is closed,

- bypass AC source input switch Q4S is open,

- inverter output switch Q5N is open,

- battery circuit breaker QF1 is open.

Signal to open battery

circuit breaker(s) QF1:

In the event the "emergency off" button is pressed or to avoid an excessive
battery discharge (lasting more than three times the rated backup time plus two
hours).

Repo Contact:

(Volt-free changeover contact) used to trip switching devices in the event of an
emergency shutdown.

"General Alarm" information:

(Volt-free changeover contact) which includes:

- internal faults.

- information on temperatures outside tolerances in the battery room (optional).

- overload information (> In).

- static-switch ventilation and power-supply faults.

NOTE

The maximum breaking capacity of the changeover contacts is 5A at 250V.

Galaxy PWUPS 100 to 225kVA

Installation

3 — 8

86-133060-00 A00