MGE UPS Systems GALAXY PW 225KVA User Manual

Page 32

Advertising
background image

2.7

System Start-up

2.7.1

Single UPS unit or Redundant Parallel UPS

Proceed in the following order: See Figure 2-7.

1.

Close the upstream switches supplying normal and bypass AC source power (on the LV switchboard).

2.

Close normal AC input switch Q1. The system powers up:

- the rectifier/charger automatically starts.

- green light 1 on the control panel goes on.

- light 2 turns red.

3.

Close bypass AC input switch Q4S:

- green lights 3 and 5 on the control panel go on.

4.

Close inverter output switch Q5N.

5.

Close battery circuit breaker QF1:

- light 2 goes off.

6.

Open maintenance bypass switch Q3BP.

7.

Press the "inverter on" button 7 on the control panel:

- the green "inverter" light 4 flashes.

- the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred

to the inverter if the on-line mode is selected.

- the green "static-bypass" light 3 goes off.

- the green "inverter" light 4 shines for on-line mode.

Figure 2-7: Single UPS Unit Start-up Diagram.