3.3

Power-Circuit Wiring Diagrams

The single UPS wire diagram is for typical UPS installations shown in Figure 3-1. The heavy lines represent the
cables that must be connected (F), refer to section 3.5 ‘Connections Between Cabinets’ for more detail on cables.

Figure 3-1: Galaxy PW™ Single UPS Unit Wire Diagram.

Legend:

1: Normal AC source,

2: Bypass AC source,

A: Rectifier/charger module,

B: Inverter module,

C: Static-bypass module,

D: Battery cabinet next to the

Galaxy PW™ UPS cabinet,

E: Additional battery cabinets,

F: The equipotential-bonding

connection between cabinets.

3.4

Hot Swap Options

The external bypass may be used to construct a bypass outside the UPS, thus making it possible to shutdown the
UPS for maintenance purposes.

The option may be used for single UPS units and redundant parallel UPS. For the power-circuit connections of a
single UPS unit see Figure 3-2, for the power-circuit connections of parallel UPS see Figure 3-3.

Power cables for UPS-to-bypass connections are not supplied.

Figure 3-2: Single UPS Unit Power Circuit Connections.

Legend:

1: Normal AC source.

2: Bypass AC source.

A: Rectifier/charger module.

B: Inverter module.

C: Static-bypass module.

D: Battery cabinet next to the
Galaxy PW™ UPS cabinet.

E: Additional battery cabinets.

F: The equipotential-bonding

connection between cabinets.

Galaxy PWUPS 100 to 225kVA

Installation

3 — 2

86-133060-00 A00

C

B

A

Q4S

Q1

Q5N

Galaxy PW

Q3BP

2

1

D

+ –

+ –

E

F

QF1

F

Q4S

2

Q3BP

Q5N

( )

( )

( )

( )

2

1

C

B

A

Q4S

D

+ –

+ –

E

F

QF1

Q1

Q5N

Galaxy PW

F

Q3BP

( )

( )