INTERNAL UPS FAULT

LOAD TRANSFER FAULT,

CALL MAINTENANCE

A fault has occurred in the static switch that transfers the load between the inverter and the bypass AC source (M2).
Servicing by the after-sales support department is required. The buzzer sounds continuously.

OVERLOAD

RATED CURRENT PER PHASE = XXXA

CHECK LOAD LEVEL

This display informs the user that load current is greater than rated current, and gives the value. The buzzer sounds
continuously.

UPS SHUTDOWN DUE T AN OVERLOAD

CHECK LOAD LEVEL

This message follows the preceding when the overload persists. The UPS has shut down and the buzzer sounds
continuously.

INVERTER NOT IN PHASE WITH MAINS 2

TRANSFER DISABLED,

CHECK MAINS 2

The phase difference between the inverter and the bypass AC source (M2) is outside tolerances. Transfer of the load
between the inverter and the bypass AC source (M2) will result in an interruption in the supply of power to the load.

For parallel UPSs, this message should be interpreted as meaning the phase difference between the inverter for
which the message is displayed and the other inverters is outside tolerances.

UPS SHUTDOWN

BY AN EXTERNAL COMMAND

The inverter has received a command to shut down. The command is in the form of a signal from received the
remote-indications relay board which has been set for this function.

The inverter is started again.

MAINS 2 INPUT SWITCH Q4S IS OPEN

The bypass AC source (M2) input switch Q4S is open, i.e. backup power for the load via the bypass AC source (M2)
is not available.

INVERTER OUTPUT SWITCH Q5N IS OPEN

Inverter output switch Q5N is open, i.e. the load cannot be supplied via the inverter.

BYPASS SWITCH Q3BP IS CLOSED

Maintenance bypass switch Q3BP is closed. The system is in maintenance configuration and the load is supplied
by the bypass AC source.

STATIC SWITCH (M2) OFF

DUE TO AN OVERLOAD

The load is no longer supplied by the bypass AC source (M2), due to an extended overload. The buzzer sounds
continuously.