3 manual ope ra tion 22, Manual operation, 3manual operation – Samson 5476 User Manual

Page 22

Advertising
background image

3

Manual operation

Heating circuit and DHW circuit (Anl 9: underfloor heating circuit) can be set to manual mode
at their operating mode selector switches.

Heating circuit mode selector switch

The heating circuit can only be set to manual mode when the DHW/underfloor heating circuit
mode selector switch is not positioned at

.

+

0

Anl 1, 2, 3

UP1 on, SLP/TLP off,
valve RK1 opens

UP1 on, SLP/TLP off,
valve RK1 stationary

UP1 off, SLP/TLP off,
valve RK1 closes

Anl 4, 5, 6, 11

UP1 on,
valve RK1 opens

UP1 on,
valve RK1 stationary

UP1 on,
valve RK1 closes

Anl 7, 8

UP1 on,
valve RK2 stationary,
valve RK1 opens

UP1 on,
valve RK2 stationary,
valve RK1 stationary

UP1 on,
valve RK2 stationary,
valve RK1 closes

Anl 9

UP1 on, SLP off,
valve RK2 stationary,
valve RK1 opens

UP1 on, SLP off,
valve RK2 stationary,
valve RK1 stationary

UP1 on, SLP off,
valve RK2 stationary,
valve RK1 closes

DHW circuit mode selector switch (system Anl 9: underfloor heating circuit)

+

0

Anl 2, 3

UP1 off, SLP/TLP on,
charging temp. control

DHW heating inactive

DHW heating inactive

Anl 4, 5, 6, 11

SLP/TLP on,
valve RK2 opens

SLP/TLP on,
valve RK2 stationary

SLP/TLP on,
valve RK2 closes

Anl 7, 8

SLP/TLP on,
valve RK1 stationary,
valve RK2 opens

SLP/TLP on,
valve RK1 stationary,
valve RK2 stationary

SLP/TLP on,
valve RK1 stationary,
valve RK2 closes

Anl 9

UP1 on, SLP on,
valve RK1 stationary,
valve RK2 opens

UP2 on, SLP off,
valve RK1 stationary,
valve RK2 stationary

UP2 on, SLP off,
valve RK1 stationary,
valve RK2 closes

Note!
In manual mode, frost protection is not guaranteed (–> section 7.2).

22

EB 5476 EN

Manual operation