For ced char ging, dhw sto ra ge tank 56, For ced char ging, pumps 56, Ther mal dis in fec ti on 56 – Samson 5476 User Manual

Page 56: Thermal disinfection of the dhw storage tank

Advertising
background image

Set-back difference by set-back of the current flow temperature.
The amount of time in which the priority for the DHW circuit is given is set in the

Priority in case

of deviation parameter.

Function

WE

Configuration

Priority for
DHW circuit

OFF
10 min

FB8 = ON, Ab
Priority in case of deviation / 2 to 10 min

6.10 Forced charging of the DHW storage tank

(Anl 2, 3, 5, 7, 8 and 9)

This function is always configured when the system has at least one storage tank sensor.
To provide the full room heating performance when the time-of-use of the heating circuits be-
gins, existing storage tanks are charged one hour before the time-of-use of the heating circuits
starts.

6.11 Thermal disinfection of the DHW storage tank

In all systems with DHW heating, the DHW storage tank is thermally disinfected on a selected
day of the week or every day. The storage tank is heated up to 70 °C. Thermal disinfection starts
at 0.00h and finishes at 4.00h at the latest.

Thermal disinfection for preventing legionella infection causes

4

high return flow temperatures during the disinfection cycle (return flow temperature limita-
tion suspended),

4

high storage temperatures after thermal disinfection has been concluded,

4

lime scale (possibly), which can have a negative effect on heat exchanger performance.

Note!
This function is not available when a storage tank thermostat is used.

Function

WE

Configuration

Thermal disinfection

OFF
3 (Mi)

FB7 = ON
Day of the week / 1–7 = daily, 1, 2 to 7 = Mon, Tue to Sun

56

EB 5476 EN

Functions of the DHW circuit

Advertising