16 Sensor selection

OFF All FB16 = ON; select: P1000: Pt 1000 and Pt 100 sensors*

ntc:

NTC and Pt 100 sensors*

FB16 = OFF: PTC and Pt 100 sensors*
* A mixture of both types of sensor is possible

17 Control mode

three-step RK2

ON 4, 5,

6, 7,
8, 9,

11

FB17 = ON: Three-step signal control mode
Function block parameters

:

K

P

(proportional gain) / 0.1 to 50 (0,5)

T

N

(reset time) / 1 to 999 s (Anl 5, 6: 60 s; Anl 4: 200 s)

T

Y

(val. transit time) / 15, 30 to 240 s (Anl 5, 6: 30 s; Anl 4: 90 s)

FB17 = OFF: On/off control
Function block parameter

:

Hysteresis / 1 to 30 °C (5 °C)

18 Outdoor

temperature –
current input

OFF All FB18 = ON: Current input to measure outdoor temperature

activated
Select:

0: 0 to 20 mA = –20 to 50 °C
4: 4 to 20 mA = –20 to 50 °C

A 50-

W

resistor must be connected to terminals 7 (+) and GND

(terminals ½) in parallel to the current signal
FB18 = OFF: Sensor input for measuring outdoor temperature

19 4-point

characteristic

OFF

FB19 = ON: Characteristic according to four points
FB19 = OFF: Characteristic according to gradient

20 Return flow sensor

RüF1

ON

All FB20 = ON: Return flow sensor activated

Function block parameter:
Limiting factor / 0.1 to 10 (1)
Selection with systems Anl 2, 7 and 9:
SLP (thermometer and heat exchanger icons) switched on de-
pending on return flow temperature or SLP switched on irrele-
vant of return flow temperature
Setting only possible after entering key number!

21 Return flow sensor

RüF2

OFF 4, 5,

11

FB21 = ON: Return flow sensor RüF2 activated
Function block parameter:
Limiting factor / 0,1 to 10 (1)
Selection with system Anl 5:
SLP (thermometer and heat exchanger icons) switched on de-
pending on return flow temperature or SLP switched on irrele-
vant of return flow temperature
Setting only possible after entering key number!

EB 5476 EN

83

Appendix