Samson 5476 User Manual

Page 86

Advertising
background image

FB Function

WE Anl Comments

36

(12)

to

43

(19)

BE8

to

BE1

All FB36 to 43 = ON: Binary input in error status register

Select:

StEIG: Fault indicated by rising edge/make contact
FALL: Fault indicated by negative edge/break contact

44

(20)

Modem operation

OFF All Select: 8-bit:

8-bit addressing

16-bit: 16-bit addressing

FB44 = ON: Modem function activated
Function block parameters:
Cyclical initialization In / 0 to 255 min (30 min)
Intervals between dialing PA / 0 to 255 min (5 min)
Modem timeout t

0

/ 0 to 99 min (5 min)

Dialing procedure/ PULS/ton (PULS)
Phone number of station GLT / 0 to 9, P, -; max. 23 characters
Setting only possible after entering key number!

45

(21)

Dial-up also upon
corrected fault

OFF All FB45 = ON: Dial-up when faults exist/remedied

FB45 = OFF: Dial up only when faults exist
Setting only possible after entering key number!

46

(22)

Phone number of
alternative recipient

OFF All FB46 = ON: Dialing an alternative recipient

Function block parameters:
Number of dialing attempts An / 0 to 99 (5)
Phone number of alternative recipient / 0 to 9, P, -; max. 23 char.
Setting only possible after entering key number!

47

(23)

Fault alarm output
BA8

OFF All FB47 = ON and FSr > 0: BA8 = ON

Pump management for UP1 no longer available
Setting only possible after entering key number!

FB Function block, WE Default setting, Anl System code number

86

EB 5476 EN

Appendix