Samson 5476 User Manual

Page 85

Advertising
background image

FB Function

WE Anl Comments

29
(5)

Meter bus

OFF All FB29 = ON: Meter bus communication activated

Function block parameters WMZ 1 to 3:
Meter bus address / 0 to 255 (WMZ1: 254; WMZ2, 3: 255)
Model code / 1434, CAL3, APAtO, SLS (1434)
Reading mode / 24h, Cont CoiL (Cont)
Setting only possible after entering key number!

30
(6)

Flow rate limitation OFF All FB30 = ON: Flow rate limitation activated

Select:

At: Outdoor temperature dependent limitation,

FB19 = ON when “At“ selected
---: Fixed limitation

Function block parameters:
Max. limit / 0.01 to 650 m

3

/h (2 m

3

/h)

Max. limit for heating* / 0.01 to 650 m

3

/h (2 m

3

/h)

Max. limit for DHW / 0.01 to 650 m

3

/h (2 m

3

/h)

Min. limit / 0.01 to 100 m

3

/h (---)

Limiting factor / 0.1 to 10 (1)
* Parameter does not need to be set when “At“ selected
Setting only possible after entering key number!

31
(7)

Capacity limitation OFF All FB31 = ON: Capacity limitation activated

Select:

At: Outdoor temperature dependent limitation,

FB19 = ON when “At“ selected

---: Fixed limitation

Function block parameters:
Max. limit / 0.1 to 6000 kW (15 kW)
Max. limit for heating* / 0.1 to 6000 kW (15 kW)
Max. limit for DHW / 0.1 to 6000 kW (15 kW)
Limiting factor / 0.1 to 10 (1)
* Parameter does not need to be set when “At“ selected
Setting only possible after entering key number!

32
(8)

Circulation over
heat exchanger

OFF

5,

11

FB32 = ON: Control of DHW circuit remains released after
storage tank charging
Setting only possible after entering key number!

33
(9)

Sensor calibration

ON

All Cannot be deactivated

Setting only possible after entering key number!

34

(10)

Manual level
locking

OFF All FB34 = ON: Locking activated

Setting only possible after entering key number!

35

(11)

Lock dial-up

OFF All

FB35 = ON: No dial-up in case of fault
Setting only possible after entering key number!

EB 5476 EN