The measured temperature reading (return flow temperature) and the set point reading (flow
temperature of the heating, charging temperature) blink to indicate that a return flow limitation
is active in the control circuit concerned. In systems Anl 2, 3, 7, 8 and 9, the

Return flow limita-

tion temperature parameter during DHW heating is used for limitation in the primary circuit
while the DHW heating is active. The systems Anl 4, 5, 6 and 11 allow a separate return flow
sensor to be installed in the DHW circuit.
To ensure that the preset

Return flow temperature limit temperature during DHW heating can be

met, make sure that:
– the heating characteristic is not adjusted to ascend too steeply,
– the speed of the circulation pumps is not set too high,
– the heating systems have been calibrated.

Note!
For outdoor temperature dependent control with gradient characteristic, the return flow tempe-
rature is limited to fixed set point by entering the same value for both Maximum return flow tem-
perature

and Minimum return flow temperature parameters.

Functions

WE

Configuration

Return flow sensor RüF1

ON
1

FB20 = ON
Limiting factor / 0.1 to 10

Return flow sensor RüF2

OFF
1

FB21 = ON
Limiting factor / 0.1 to 10

Parameters

WE

Range of values

Gradient, return flow

1.2

0.2 to 3.2

Level, return flow

0 °C

–30 to 30 °C

Maximum return flow temperature

65 °C

20 to 90 °C

Minimum return flow temperature

65 °C

20 to 90 °C

Return flow temperature limit temperature during
DHW heating

65 °C

20 to 90 °C

Note!
In systems Anl 2, 5, 7 and 9 The function block setting FB20 = ON or FB21 = ON provides two
switching conditions for the storage tank charging pump (SLP) that can be selected when the
heating circuits are switched off:
(1) SLP switched on regardless of the return flow temperature
(2) SLP switched on depending on the return flow temperature

58

EB 5476 EN

System-wide functions