Stop storage tank charging

The controller stops charging the storage tank when the water temperature in the storage tank
measured at sensor SF1 reaches the value T =

DHW heating ON + Hysteresis. In systems with

two storage tank sensors, the controller stops charging the storage tank when the water temper-
ature in the storage tank measured at sensor SF2 reaches the value

DHW heating OFF. In sys-

tems with storage tank thermostat, the

Hysteresis of the thermostat determines when the storage

tank charging is finished.

DHW heating from the secondary circuit

(Anl 3, 8):

When a high flow temperature is required by the system, the heat exchanger charging pump is
immediately switched off. If no heating is taking place or if the flow temperature demand in the
system is lower, the

End charging process parameter applies for switching off the heat

exchanger charging pump.
The heat exchanger charging pump is switched off at the latest after two transit time periods of
the control valve (2 x T

Y

); 15 seconds after the heat exchanger charging pump has been

switched off, the storage tank charging pump stops operating.

DHW heating from the primary circuit

(Anl 5, 11):

The storage tank charging pump (Anl 5) or the heat exchanger charging pump (Anl 11) is
switched off when the temperature reaches

End charging process parameter, at the latest, how-

ever, two transit time periods of the DHW control valve (2 x T

Y

).

In system Anl 11, 15 seconds after the heat exchanger charging pump has been switched off,
the storage tank charging pump stops operating.

Functions

WE

Configuration

Storage tank sensor SF1

ON

FB14

Storage tank sensor SF2

ON

FB15

Flow sensor VF3

OFF

FB27

Parameters

WE

Range of values

DHW heating ON

45 °C

20 to 90 °C

DHW heating OFF

50 °C

20 to 90 °C

Hysteresis

5 °C

0 to 30 °C

Charging temperature

55 °C

20 to 90 °C

End charging process

53 °C

20 to 90 °C

Heat exchanger inlet temperature limit

120 °C

20 to 130 °C