5.1.2 4-point characteristic

The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points for the

Outdoor temperature, the Flow temperature and the Return flow

temperature. The Set-back difference at points 2 and 3 indicates how much the flow temperature
is reduced outside the times-of-use. The

Max. flow temperature and Min. flow temperature pa-

rameters mark the upper and lower limits of the flow temperature.

Function

WE

Configuration

Characteristic

OFF

FB19 = ON

Parameters

WE

WE*

Range of values

Outdoor temperature, point 1
Outdoor temperature, point 2
Outdoor temperature, point 3
Outdoor temperature, point 4

–15 °C

–5 °C

5 °C

15 °C

–15 °C

–5 °C

5 °C

15 °C

–30 to 20 °C

Flow temperature, point 1
Flow temperature, point 2
Flow temperature, point 3
Flow temperature, point 4

70 °C

55 °C
40 °C
25 °C

50 °C

40 °C
35 °C
20 °C

20 to 130 °C

Return flow temperature, point 1
Return flow temperature, point 2
Return flow temperature, point 3
Return flow temperature, point 4

65 °C
50 °C
35 °C
20 °C




20 to 90 °C

Set-back difference, points 2, 3

20 °C

5 °C

0 to 50 °C

Max. flow temperature

90 °C

50 °C

20 to 130 °C

42

EB 5476 EN

Functions of the heating circuit

Fig. 3 · 4-point characteristic

P1 to P4

Points 1 to 4

t

VL

Flow temperature

t

A

Outdoor temperature

... min

Minimum flow temperature

... max

Maximum flow temperature

-----

Set-back characteristic