7.5

Condensate accumulation control

Activate the Limitation of the system deviation for OPEN signal function to start up condensate
accumulation plants, in particular to avoid problematic excess temperatures. The controller re-
sponse to set point deviations which cause the primary valve to open is attenuated. The control-
ler response to set point deviations which cause the control valve to close remains unaffected.

Function

WE

Configuration

Limitation of the system deviation for
OPEN signal RK1/RK2

OFF
2 °C

FB11/FB12 = ON
Maximum system deviation / 2 to 10 °C

Note!
The condensate accumulation control function can only be activated when no on/off control has
been configured, i.e. when FB10 = ON or FB17 = ON.

7.6

Three-step control

The flow temperature can be controlled using a PI algorithm. The valve reacts to pulses that the
controller emits when a system deviation occurs. The length of the first pulse, in particular, de-
pends on the extent of the system deviation and the selected

Proportional gain K

P

(the pulse

length increases as K

P

increases). The pulse and pause lengths change continuously until the

system deviation has been eliminated. The pause length between the single pulses is greatly in-
fluenced by the

Reset time T

N

(the pause length increases as T

N

increases).

The

Transit time T

Y

specifies the time required by the valve to travel through the range of 0 to

100 %.

Functions

WE

Configuration

Three-step control for RK1

ON
0.5
200 s
90 s
2 x T

Y

FB10 = ON
K

P

(proportional gain) / 0.1 to 50

T

N

(reset time) / 1 to 999 s

T

Y

(valve transit time) / 15 to 240 s

Pump lag time / 1 x T

Y

to 10 x T

Y

Three-step control for RK2

ON
0.5
60 s*
30 s*

FB17 = ON
K

P

(proportional gain) / 0.1 to 50

T

N

(reset time) / 1 to 999 s

T

Y

(valve transit time) / 15 to 240 s

* WE applies to systems Anl 5, 6; T

N

= 200 s, T

Y

= 90 s applies for system Anl 4

EB 5476 EN

59

System-wide functions