12 appen dix 82, 1 function block list 82, Appendix – Samson 5476 User Manual

Page 82: Function block list

Advertising
background image

FB Function

WE Anl Comments

9 Parallel pump

operation

OFF 2, 3,

9

FB9 = ON: Parallel pump operation
Select

(Anl 2 and 9):

PU: Parallel pump operation
US: Operation with switchover valve
Function block parameter

(on selecting: US):

Stop parallel oper. in case of deviation / 2 to 10 min (10 min)
FB9 = OFF: Intermediate heating after 20 min
Select

(FB9 = ON, US or FB9 = OFF):

20: Intermediate heating after 20 min
– –: No intermediate heating

10 Control mode

three-step RK1

ON

All FB10 = ON: Three-step signal control mode

Function block parameters

:

K

P

(proportional gain) / 0,1 to 50 (0,5)

T

N

(reset time) / 1 to 999 s (200 s)

T

Y

(valve transit time) / 15, 30, 45 to 240 s (90 s)

Pump lag time / 1 x T

Y

to 10 x T

Y

(2 x T

Y

)

FB10 = OFF: On/off control; when FB10 = OFF also FB11 = OFF
Function block parameter

:

Hysteresis / 1 to 30 °C (5 °C)

11 Limit deviation for

OPEN signal RK1

OFF All FB11 = ON, only when FB10 = ON: Limitation active

Function block parameter

:

Max. deviation / 2 to 10 °C (2 °C)

12 Limit deviation for

OPEN signal RK2

OFF

4

to

11

FB12 = ON, only when FB17 = ON: Limitation active
Function block parameter

:

Max. deviation / 2 to 10 °C (2 °C)

13 Room sensor RF

OFF All FB13 = ON: Sensor/remote operation activated

Cannot be selected when FB0, FB1 or FB2 = ON;
when FB0, FB1 and FB2 = OFF the room temperature is only
indicated and not used for the control

14 Storage tank sensor

SF1

ON 2, 3,

5, 7,
8, 9,

11

FB14 = ON: Sensor SF1 activated
Storage tank thermostat: FB14 = FB15 = OFF

15 Storage tank sensor

SF2

ON

with

3, 5,

8,11

2, 3,
4, 5,
7, 8,
9,11

FB15 = ON: Sensor SF2 activated
Select:

--: Settings for plants with DHW heating in storage tank

charging system with 2 storage tank sensors

CF: Activated for solar circuit

Storage tank thermostat: FB14 = FB15 = OFF

82

EB 5476 EN

Appendix

Advertising