7.7

On/off control

The flow temperature can be controlled by an on/off signal. The controlled valve is opened
when the flow temperature falls below the set point by T = 0.5 x

Hysteresis. When the flow tem-

perature exceeds the set point by T = 0.5 x

Hysteresis, the control valve is closed. The greater the

Hysteresis selected, the lower the switching frequency.

Function

WE

Configuration

On/off control for RK1/RK2

ON
5 °C

FB10/FB17 = OFF
Hysteresis / 1 to 30 °C

7.8

Releasing a control circuit over the binary input

The release of a control circuit using the binary output only becomes effective when the respec-
tive control circuit is in automatic mode (icon

).

The released control circuits always work in automatic mode; the deactivated control circuit be-
haves as if it were in frost protection mode if the outdoor temperature requires it. The control cir-
cuit can be released via the binary input when the binary input is open (BE = ON).

Function

WE

Configuration

Releasing a control circuit

OFF

FB25 = ON, FErn

Note!
The function cannot be selected in systems Anl 4, 5 and 9 with solar system and in system
Anl 11 with VF3.

7.9

Processing of external demand in RK1

Regardless of the operating mode, except form manual mode, of the control circuit RK1, the
controller uses the

Minimum flow temperature for external demand when the binary input is

closed (BE1 = ON). The DHW heating from the secondary circuit and demands of the heating
circuit which are higher than the

Minimum flow temperature for external demand have priority.

In systems Anl 7 and 8, a mixing control is not active, just the set point of the heating circuit
changes.
The deactivated binary input (BE1 = OFF) does not have any effect on the control.

Function

WE

Configuration

External demand over BE1 OFF

20 °C

FB25 = ON, bed
Minimum flow temperature for external demand / 20 to 130 °C

60

EB 5476 EN

System-wide functions