73 appendix – Samson 5476 User Manual

Page 73

Advertising
background image

Function

WE

Configuration

Flow rate limitation

OFF

2.0

m

h

3

2.0

m

h

3

2.0

m

h

3

2.0

m

h

3

1.0

FB30 = ON
At/---
Maximum limit / 0.01 to 650

m

h

3

Maximum limit for heating* / 0.01 to 650

m

h

3

Maximum limit for DHW / 0.01 to 650

m

h

3

Minimum limit/ 0.01 to 650

m

h

3

Limiting factor / 0.1 to 10.0
* Does not need to be set on selecting “At“

Parameter

*

WE

Range of values

Maximum limit for heating, points 1 to 4

2.0 m

3

/h 0.01 to 100 m

3

/h

* Parameter only needs setting with FB30 = ON, select “At“

Capacity limitation
The settings which are to made for the capacity limitation are mainly contained in function block
FB31 as function block parameters. Only after selecting the type of limitation “At“ for outdoor
temperature dependent limitation (which automatically means a 4-point characteristic), four
outdoor temperature dependent maximum limits for heating need to be set in the 4-point char-
acteristic menu. After selecting “- - -“, set

Maximum limit for the system, Maximum limit for heat-

ing and Maximum limit for DHW, Minimum limit and the Limiting factor that appear in this order.
The

Limiting factor determines how strongly the controller responds when the limit values are ex-

ceeded in either direction.

Function

WE

Configuration

Meter bus

OFF
254**
1434
Cont

FB29 = ON
Meter bus address for WMZ 1 to 3 (ST.-NO) / 0 to
255
Model code WMZ 1 to 3 / 1434, CAL3, APAtO, SLS
Reading mode WMZ 1 to 3 / 24h, Cont, CoiL

Capacity limitation

OFF
15 kW
15 kW
15 kW
1.0

FB31 = ON
Maximum limit / 0.01 to 6000 kW
Maximum limit for heating* / 0.1 to 6000 kW
Maximum limit for DHW / 0.1 to 6000 kW
Limiting factor / 0.1 to 10.0

*

Does not need to be set on selecting “At“

** WE for WMZ2 and 3: 255

Parameter

*

WE

Range of values

Maximum limit for heating, points 1 to 4

15 kW

0.1 to 6000 kW

EB 5476 EN

73

Appendix