Systems That Require Contact Closure

1 This system has been set for the default alarm configuration. For

installations that require contact closures, rather than a serial interface, set

the system for the AS/400 configuration as described in the manual shipped

with this product.
The AS/400 configuration provides alarms, which are normally open when

the alarm is not present and closed when an alarm occurs. This

configuration does not have serial output.

2 Connect the alarm adapter to the unit's RSĆ232 port and the modular

output to the computer, wallfield, etc. through an 8Ćpin modular plug.

Comcode

PEC

For 3B2 systems, use:

406707737

24024

For all other systems, use:

407691401

24433

Systems That Require a Serial Interface

1 Refer to the manual shipped with the product to configure the system for

the appropriate serial interface.

2 The alarm information is provided by the unit's RSĆ232 connector via the

serial output pins and does not require an adapter/interface.

UPS with Bypass Module Installation

The Bypass Module is available in a 60ĆHz Distribution Module or a 50ĆHz Isolation

Module, each with a plug/receptacle or hardwired option. The Bypass Modules have

a Maintenance Bypass feature that supplies power to your equipment even when the

UPS electronics are removed for maintenance or upgrades. The Bypass Distribution

Module also provides 120V output.

Use the following procedure to install the UPS with a Bypass Module:

1 Place the UPS near the equipment to be protected. Make sure the UPS is

well ventilated and away from direct sunlight or other heat source.
Do not place more than three battery modules in one stack. The modules

must be stacked in the correct order (Figure 3 shows the Distribution

Module and Figure 4 shows the Isolation Module).

NOTE

You can install additional battery modules while the UPS is operating, but make

sure the UPS is not in Battery Mode (see page 39).