Ups communications interface port – Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page 61

Advertising
background image

Communication 5

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

51

UPS Communications Interface Port

In addition to configuring the UPS for specific communication options, you must

also ensure proper use of the serial port when connecting the UPS to your network

or monitoring equipment.

NOTE

Semiconductor switch contacts are rated at a maximum current of 50 mA and a

maximum of +40 Vdc across the contacts. Do not apply any negative voltage to these

contacts.

Use only the pins specified for your communications configuration. The use of any

additional pins for any of the following interfaces can cause interference with

system communications.

Even though your network uses the specified signal lines, the pins assigned to these

signals at the network end of the cable may vary with those of the UPS serial port.

The connector body and style may vary as well.

NOTE

Standard, pinĆforĆpin cables may not work correctly. Consult your network

software or server manuals for system shutdown pin assignments.

The UPS serial port complies with EIA RSĆ232 standards. RSĆ232 specifies a

maximum cable length of 50 feet. See Figure 21 for the location of the serial port.

UPS Rear Panel

Serial Port Detail

Serial

Port

Figure 21. Serial Port Location