Troubleshooting

7

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

58

Action

Possible Cause

Condition

No output load voltage.

Load plug(s) not fully seated.

Verify load plug(s) are fully seated.

Load circuit protectors tripped.

Reset load protectors.

OVERLOAD

I1

I2

I3

OUTPUT ON

Power requirements exceed UPS

capacity. If overload is greater

than 105%, the alarm beeps

every second and the UPS may

switch to Bypass Mode.

Your UPS continues to operate.

Reduce load.

OVERLOAD

I1

I2

I3

OUTPUT ON

The UPS switched to Bypass

Mode because the overload

increased (above 105%). The

alarm beeps.

Reduce load.

If the Overload Indicator remains lit,

reset the UPS by pressing the

Output

|

On button until the alarm

beeps.

You may need to obtain a larger

capacity UPS.

OVERLOAD

I1

I2

I3

OUTPUT ON

The utility line voltage and

frequency are out of

specification.

The inverter remains online, deriving

power from the utility until it is no

longer acceptable.

Check the unit configuration.

Refer to the product specifications

(see page 53).

OVERLOAD

I1

I2

I3

OUTPUT ON

UPS internal temperature is too

high. The alarm beeps and the

UPS switches to Bypass Mode for

approximately 10 minutes,

allowing the UPS to cool down.

Shut down the UPS. Clear vents.

Remove any heat sources. Wait

approximately 5 minutes and retry.

Contact your service representative if

condition persists.

OVERLOAD

I1

I2

Weak battery while in Normal

Mode. The alarm beeps.

Allow the battery to charge for

24 hours, then retest. Have batteries

replaced if condition persists.

I3

OUTPUT ON

Battery breaker is open (O).

Make sure the battery module breaker

is in the ON (

|

) position.

Battery module is not properly

connected to the UPS.

Make sure battery cords are

connected.