Communications mode reference chart – Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page 62

Advertising
background image

Communication

5

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

52

Communications Mode Reference Chart

The following chart defines the UPS serial port contacts. Serial communication is

not available with 3Com and AS/400 network configurations. Use only the

applicable pins for the selected communication mode; otherwise, interference

problems may occur.

Communication

Mode

Function

Signal Name

Pin No.

True Condition

Serial

Data to UPS

RS232 TxD

2

N/A

Data from UPS

RS232 RxD

3

N/A

Signal Ground

7

Novell

Battery On

ON.AC

14/16

Open

Low Battery

TWO.MIN

23/24

Closed

Signal Ground

7/15/25

Novell

(Lucent Technologies

Battery On

ON.AC

14/16

Closed

(Lucent Technologies

Default)

Low Battery

TWO.MIN

23/24

Closed

Signal Ground

7/15/25

3Com

Shutdown (Remote)

SHUT.DOWN

2

Positive Voltage

Low Battery

LOW.BATT

9

Positive Voltage

Battery On

PWR.FAIL

10

Positive Voltage

Signal Ground

7

AS/400

UPS Available

UPS Available

11/13

Closed

Battery On

Utility Failure

14/16

Closed

Bypass

UPS Offline

17/19

Closed

Low Battery

Low Battery

23/24

Closed

Signal Ground

12/15/18/25

NOTE

Pin numbers separated by a forward slash ( / ) are connected together internally.