UPS Operation

4

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

44

5 Press and hold the Output

On button until the alarm beeps again.

Two indicators, corresponding with the current setting, remain flashing.

The output voltage is factoryĆconfigured for 230V.

OVERLOAD

I1

I2

I3

OUTPUT ON

220V

230V

240V

208V

Figure 19. Output Voltage Indicators

6 Press the Output

Off button to scroll through the output voltage

options, top to bottom. Each time you press the button, the UPS beeps and

the next two indicators flash.

NOTE

If you do not save a selection within two minutes, the setup automatically aborts

and switches back to the original configuration.

7 Press and hold the Output

On button until the alarm beeps to select and

save the output voltage. Failure to release the button immediately after the

beep will cause the UPS to abort the setup.

8 Press and hold the Output

On button until you hear the UPS beep

(approximately one second).

The



Indicator remains lit and the Output On Indicator turns on,

indicating the UPS is online.

9 Turn the Bypass switch on the Bypass Module to the NORMAL position.

The front panel displays the percentage of full load being applied to the

UPS. The UPS is now in Normal Mode with the load online.